Microsoft gets two-phase immersion cooling running in an Azure data center – ZDNet

azureliquidcooling.jpg

 azureliquidcooling.jpg

Credit: Microsoft has actually been checking two-phase liquid immersion cooling innovation for a variety of years. Now, it’s beginning to execute this innovation in its Azure datacenters, beginning with its Quincy, Wash.-based ones, officials stated on April 6.

This production-environment deployment of two-phase immersion cooling is the next action on the company’s journey to deliver more effective and reputable, and more eco-friendly information centers, authorities said.Like other

major cloud suppliers, Microsoft has actually been using air to cool off processors that are getting progressively hot, specifically when running specific workloads. Since heat transfer in liquids is “orders of magnitude more efficient than air,” immersion cooling might be a much better option in time, officers state.

Google currently has actually deployed liquid cooling in its information centers to manage the high-powered demands from its Tensor Processing Unit AI processing. Microsoft’s claims of being the very first to revolve around the “two-phase” part of the immersion cooling.

With single-phase cooling, the fluid remains in liquid state, and the heat is finished natural or forced convection. In this regard, single-phase cooling resembles air cooling. The hot fluid in turn rejects heat through a heat exchanger and is distributed back, company authorities describe. But two-phase cooling happens passively. When the fluid is available in contact with heat-generating parts, the fluid modifications state from liquid to vapor and naturally increases, carrying the heat as hidden energy. The vapor rejects the heat at a condenser and naturally transforms back into the liquid kind, Microsoft officers said.

The cryptocurrency/bitcoin-mining market was a huge pioneer of liquid-immersion cooling, utilizing it to cool off chips logging digital-currency transactions. Microsoft has actually been investigating liquid immersion cooling for high-performance workloads like AI and has actually discovered that two-phase immersion cooling can minimize power intake for any provided server in between five percent to 15%, authorities stated. The servers can be overlocked (performed at elevated power) when needed without the threat of getting too hot.

Liquid cooling is a waterless innovation. The steel cooling tank in Quincy is filled with a crafted solution that allows servers to be soaked in the liquid and function as they would in any standard air-cooled rack. The fluid boils at 122 degrees F (90 degrees cooler than boiling water). The coils that run through the tank and enable vapor to condense are linked to a separate closed-loop system that utilizes fluid to move heat from the tank to a dry cooler situated outside the container that houses the tank.

For now, Microsoft has one tank running work in a hyper-scale Azure datacenter. For the next several months, the Microsoft team will carry out a series of tests on the innovation.

” Supercomputing has used this type of innovation for decades, so the threat isn’t truly that high,” stated Microsoft Distinguished Engineer Christian Belady, who also is vice president of Datacenter Advanced Development. “The objective is for us to release this in all our data center areas, but there are a number of steps prior to we get there.”

Belady kept in mind that Microsoft’s “Project Natick” undersea data center workdemonstrated the enhanced dependability of systems when humidity and oxygen are removed from an environment. Failures due to corrosion decline significantly.

” With immersion, you have a comparable thing. Essentially, you are displacing oxygen and wetness,” he said.Microsoft is continuing to investigate other liquid-cooling innovations, including cold-plate, which generally depends on tubing filled with a liquid refrigerant. Belady says Microsoft sees a potential opportunity for both, but because immersion is” a one-time style expense for the facilities,” with no engineering required in between server generations, it might discover more widespread usage.

With single-phase cooling, the fluid stays in liquid state, and the heat is carried through forced or natural convection. In this regard, single-phase cooling is like air cooling. Microsoft has actually been examining liquid immersion cooling for high-performance workloads like AI and has actually discovered that two-phase immersion cooling can reduce power intake for any given server between five percent to 15%, officials said. Liquid cooling is a waterless technology. The steel cooling tank in Quincy is filled with a crafted solution that enables servers to be soaked in the liquid and function as they would in any basic air-cooled rack.